Boiler Feed Pump Calculator UK
Estimate boiler feedwater flow, total dynamic head, discharge pressure and pump motor power for a steam boiler. Adjust the operating conditions to develop a preliminary pump duty point.
1. Boiler and feedwater details
2. Pump duty and losses
Estimated pump duty
Estimates assume steady-state water flow and user-entered hydraulic losses.
Detailed calculation breakdown
| Parameter | Calculated value |
|---|
How to calculate boiler feed pump capacity
A boiler feed pump supplies water to replace the steam leaving the boiler and the water discharged during blowdown. For UK industrial steam systems, selecting a pump requires both the required feedwater quantity and the pressure needed to overcome boiler pressure, elevation and piping resistance.
Step 1: Determine feedwater mass flow
Enter the boiler’s rated steam generation in kilograms per hour. If blowdown is expressed as a percentage of the total feedwater mass flow, the required feedwater is greater than the steam flow.
Feedwater (kg/h) = Steam production (kg/h) ÷ [1 − (blowdown % ÷ 100)]
Apply a suitable design flow margin based on the boiler operating profile and the manufacturer’s requirements. A margin is not a substitute for understanding actual peak demand.
Step 2: Convert mass flow to volume flow
Feedwater flow (m³/h) = Design feedwater (kg/h) ÷ Density (kg/m³)
Feedwater density varies with temperature and pressure. The density field is editable so a verified property value can be entered for the installation.
Step 3: Estimate total dynamic head
Pump head (m) = [(Boiler gauge pressure + extra allowance − pump suction gauge pressure) × 100,000] ÷ (ρ × 9.80665) + static elevation (m) + friction loss (m)
All pressure entries must use the same gauge reference. The extra allowance may represent a control-valve or boiler-entry pressure requirement, but it should be based on the actual system rather than added twice.
Step 4: Calculate pump and motor power
Hydraulic power (kW) = ρ × 9.80665 × Flow (m³/s) × Head (m) ÷ 1,000
Shaft power (kW) = Hydraulic power ÷ Pump efficiency (decimal)
Apply the selected motor margin to the shaft power. Choose an actual motor and pump from the manufacturer’s performance curves and consider motor efficiency, drive requirements, operating envelope and start-up conditions separately.
Worked example: 2,000 kg/h steam boiler
Assume steam production of 2,000 kg/h, 5% blowdown of feedwater, 15% flow margin and water density of 971.8 kg/m³. The feedwater requirement before margin is approximately 2,105 kg/h. Design mass flow is approximately 2,421 kg/h, or 2.49 m³/h.
With a boiler pressure of 10 bar(g), 1 bar additional pressure allowance, suction pressure of 0 bar(g), 5 m elevation and 12 m friction loss, the estimated head is about 132.4 m. At 65% pump efficiency, the required shaft power is about 1.36 kW, before motor margin. These are illustrative values, not a pump recommendation.
Typical considerations for UK boiler feed pumps
| Design consideration | Why it matters |
|---|---|
| Feedwater temperature | Changes density, vapour pressure and cavitation risk |
| NPSH available | Must exceed the pump’s required NPSH with appropriate margin |
| Boiler pressure and control valve | Determine discharge pressure and pump head |
| Blowdown and peak demand | Affect required feedwater capacity |
| Standby pumps and minimum flow | Support reliability and protect the pump at low flow |
| Pressure Equipment (Safety) Regulations / PSSR | May affect equipment and system compliance, inspection and safe operation |
Boiler feed pump FAQs
What is a boiler feed pump calculator?
It estimates the water flow, differential head and power needed for a pump supplying feedwater to a steam boiler. It is a preliminary design aid.
How do I calculate boiler feed pump flow rate?
Start with steam production, account for boiler blowdown, add an appropriate design margin, then divide mass flow by feedwater density to obtain m³/h.
What is the difference between pump head and pressure?
Head represents energy per unit weight of liquid and is expressed in metres. Pressure is force per unit area, commonly bar. Conversion depends on liquid density.
What pump pressure is needed for a 10 bar boiler?
The pump must overcome the boiler pressure plus relevant elevation, friction and control-valve or entry losses, accounting for suction pressure. A 10 bar boiler does not automatically mean a 10 bar pump differential.
Does feedwater temperature affect pump sizing?
Yes. Temperature affects water density and vapour pressure. Hot feedwater can increase cavitation risk, so NPSH calculations are particularly important.
What is NPSH and why is it important?
Net positive suction head indicates the margin above the liquid’s vapour pressure at the pump inlet. The available NPSH must be assessed against the manufacturer’s required NPSH, with suitable margin.
Can this calculator select an actual pump model?
No. Final pump selection requires performance curves, efficiency at the duty point, NPSH data, material compatibility, minimum flow, operating conditions and applicable standards.
Does this calculator work for UK industrial steam boilers?
It uses metric units commonly used in UK engineering and is suitable for preliminary estimates for many steam boiler systems, subject to independent engineering verification.
How much spare capacity should a boiler feed pump have?
There is no universal allowance. Select capacity according to boiler manufacturer requirements, load variations, control strategy and redundancy provisions rather than relying solely on a generic percentage.
References for further engineering verification: HSE pressure systems guidance and UK Pressure Equipment (Safety) Regulations guidance.